Pure Sine Wave Inverter

T Series 1KVA to 3KVA Telecom Inverter

Key features: T series pure sine wave inverter/power inverter/inverter power supply is a new device which can invert the DC to AC, especially design for the communication system. ►Software protection and hardware protection, high reliabil
Key features:
 

T series pure sine wave inverter/power inverter/inverter power supply is a new device which can invert the DC to AC, especially design for the communication system.
 
►Software protection and hardware protection, high reliability
►Perfect protection: input polarity reverse, input over/under voltage, over current, short circuit, over heat, also the soft start function.
►3 layers composite filter and magnetism shielded which and reduce the reflect noise voltage to the input port, perfect electromagnetism compatibility.
►Intelligent fan
►Support pure sensibility load(should reduce voltage)
 
Technical specifications:
 
Model Parameters T1KL T2KL T3KL
Rated power VA/W 1000VA/800W 2000VA/1600W 3000VA/2400W
AC input Input system Single phrase & earth ground
Ranged voltage 220VAC
Frequency 50Hz
Voltage range 115~300VAC
Frequency range 45~55Hz
Voltage range of bypass 80VAC~285VAC
DC input DC nominal voltage 24VDC/48VDC/110VDC/220VDC
24V Nominal current 40.0A 78.4A 117.6A
Voltage range 20-29VDC
Input low voltage/protection 20/21VDC
Input high voltage/protection 29/29VDC
48V Nominal current 19.6A 39.2A 58.8A
Voltage range 40-58VDC
Input low voltage/ protection 40/42V
Input high voltage alarm/protection 58/58V
110V Nominal current 8.6A 17.2A 25.8A
Voltage range 90-130V
Input low voltage/protection 90/95V
Input high voltage/protection 130/130V
220V Nominal current 4.3A 8.6A 12.9A
Voltage range 180-260V
Input low voltage/protection 180/190V
Input high voltage/protection 260/260V
AC Output Output system Single phase & earth ground
Output voltage 220VAC±3%(inverter output)
Output frequency 50±5Hz(normal), 50Hz±1%(abnormal)
Dynamic voltage transient range <5%
Dynamic transient restore < 60ms
Waveform Sine wave THD<3%(linear load), sine wave THD<8% (nonlinear load)
Output power factor 0.8
Overload capability 105~125%≥ 60s, 126~150%≥30s, the recover point is 90%
Input current peak coefficient 3:1
Transfer time 0ms
Panel indicator system LED screen + LCD indicator, show the status of inverter and operation parameter
Communications RS232(turn to 485), stem node
Alarm function AC/DC input under abnormal, overload condition and inverter problems
Protection function AC input or output above or below the range of voltage Overload, over temperature and short circuit protection
Conduction Satisfy YD/T983-1998A
Radiation Satisfy YD/T983-1998A
Noise immunity Satisfy YD/T983-1998A
Insulating resistance > 2MΩ(500VDC)
Insulating strength 2121VDC(AC input, output to ground, DC input to AC output, without flashover in one minute)
Cooling system Wind cooling
Frequency <55dB(1M)
Working
environment
Temperature -10'C~+40'C
Humidity 0~95%, no condensation
Altitude ≤1500M, satisfy GB3859.2-93
Storage
environment
Inverter temperature -40'C~+65'C
Humidity 0~95%, no condensation
Dimensions(W×D×H)(mm) 438×380×83