General specifications: |
Input wave form: |
Sine wave(Utility or generator) |
Nominal voltage: |
120VAC |
230VAC |
Low voltage trip: |
80V/90V+/-4% |
184V/154V+/4%- |
Low voltage re engage: |
90V/100V+/-4% |
196V/164+/-4% |
High voltage trip: |
140V+/-4% |
253V+/-4% |
High voltage re engage: |
135V+/-4% |
243V+/-4% |
Max input AC voltage: |
150VAC |
270VAC |
Nominal input frequency: |
50Hz or 60Hz(Auto detect) |
Low frequency trip: |
47Hz for 50Hz, 57Hz for 60Hz |
High frequency trip: |
55Hz for 50Hz, 65Hz for 60Hz |
Output wave form: |
(Bypass mode) same as input |
Overload protection: |
Circuit breaker |
Short circuit protection: |
Circuit breaker |
Transfer switch rating: |
30 amp or 40 amp |
Efficiency on line transfer mode: |
95%+ |
Line transfer time: |
10 ms typical |
Bypass without battery connected: |
Yes |
Max bypass current: |
30 amp or 40 amp |
Bypass over load current: |
35 amp or 45 amp: alarm |
Inverter specification/output |
Output wave form: |
Pure sine wave |
Output continuous power watts: |
1000 |
2000 |
3000 |
4000 |
5000 |
6000 |
Output continuous power VA: |
1000 |
2000 |
3000 |
4000 |
5000 |
6000 |
Power factor: |
0.9-1.0 |
Nominal output voltage rms: |
120/230VAC |
Output voltage regulation: |
+-/10% rms |
Output frequency: |
50Hz+/-0.3Hz or 60Hz+/-0.3Hz |
Nominal efficiency: |
>88% |
Surge ratings: |
3000 |
6000 |
9000 |
12000 |
15000 |
18000 |
Short circuit protection: |
Yes, fault after 1 sec |
THD |
<10% |
Inverter specification/input: |
Nominal input voltage: |
12.0V |
24.0V |
48.0V |
Minimum start voltage: |
10.0V |
20.0V |
40.0V |
Low battery alarm: |
10.5V/11.0V |
21V/22.0V |
42.0/44.0V |
Low battery trip: |
10.0V/10.5V |
20.0V/21V |
40.0V/42V |
High voltage alarm: |
16.0V |
32.0V |
64.0V |
Low battery voltage recover |
15.5V |
31.0V |
62.0V |
Power saver: |
Below 25 watts when enabled |
Power saver: |
Same switched on/off on remote |
Charger mode specifications: |
Input voltage range: |
90-135VAC |
194-243VAC/164-243VAC(W) |
Output voltage: |
Dependent on battery type |
Max charger current: |
35A/70A (Charger current controller) |
Battery initial voltage for start up: |
10-15.7V for 12V(*2 for 24V; *4 for 48V) |
Over charger protection shutdown: |
15.7V for 12V(*2 for 24V; *4 for 48V) |
Charger curves (4 stage constant current) battery types |
4 steps digital controlled progressive charge |
Battery type: |
Fast V |
Float V(*2 for 24V; *4 for 48V) |
GEL U.S.A. |
14.0 |
13.7 |
A.G.M. 1 |
14.1 |
13.4 |
A.G.M. 2 |
14.6 |
13.7 |
Sealed lead acid |
14.4 |
13.6 |
GEL Euro |
14.4 |
13.8 |
Open lead acid |
14.8 |
13.3 |
Calcium |
15.1 |
13.6 |
De-sulphation |
15.5 for 4 hrs |
Remote control/RS232/USB |
Yes, optional |
Mounting |
Wall mount |
Size: in mm |
1000 model: 520*315*300 mm3 |
|
2000/3000 model: 580*315*300 mm3 |
4000/5000/6000 model: 740*315*300 mm3 |
Gross weight: |
1000 |
2000 |
3000 |
4000 |
5000 |
6000 |
20Kg |
22Kg |
26Kg |
37Kg |
47Kg |
47Kg |